Model: F60S-11
USAF Part Number 9454100-5

F6011
Online Manual View Online Technical Manuals

Description & Use The Keco Model F60S-11 Air Conditioning Unit is a horizontal configuration. The evaporator inlet and outlet flanges provide for attachment of free discharge grilles or flexible duct adapters. Two fork lift channels are provided for lifting using a standard fork lift. The supply and return ducts as well as power cable and drain hose with fittings can be stored inside the unit.

A centrifugal electric motor driven blower is used to circulate shelter air through the unit. Heating the shelter air is accomplished by two-step electric strip heaters. Cooling the shelter air is accomplished by an electrically operated mechanical refrigeration system.

The air conditioning units can be stacked three high for storage and bolted together using attached hardware.

Evaporator Air Flow
At 1.0" H20 Static Pressure
 
2000 CFM

Power Input 208 V, 50/60 Hz, 3 Ph

Power Consumption 10.5 KW

Refrigerant R-22

Refrigerant Charge 9 lbs

Weight 1000 lbs

Storage Temperature -60o F to +160o F

Operating Temperature 50o F to +125o F

Dimensions: (Facing Controls)
Width
Height
Depth (Length)


48.00"
32.75"
72.00"

Cooling Capacity Specifications
At 60 HZ, 1.0 Inch Water Gauge Static Pressure:

Ambient
(oF)

Evaporator Inlet
(oF)

Minimum Cooling Capacity
Dry Bulb
Dry Bulb
Wet Bulb
BTU/Hour
125
90
65
50,000
115
85
70
54,000
95
80
67
60,000
50
80
58
70,000

Heating Capacity Specifications

Operating Mode

Minimum Heating Capacity
BTU/Hour
Low Heat
16,800
High Heat
31,000